NOGRR282
Summary
| Title | Board Priority - Large Computational Load Ride-Through Requirements |
|---|---|
| Next Group | |
| Next Step | |
| Status | Approved on 07/09/2026 |
| Effective Dates |
08/01/2026
|
Action
| Date | Gov Body | Action Taken | Next Steps |
|---|---|---|---|
| 07/09/2026 | PUCT | Approved | |
| 06/02/2026 | BOARD | Recommended for Approval | PUCT for consideration |
| 04/29/2026 | TAC | Recommended for Approval | Board for consideration |
| 04/02/2026 | ROS | Recommended for Approval | TAC for consideration |
| 12/04/2025 | ROS | Deferred/Tabled | ROS for consideration |
Voting Record
| Date | Gov Body | Motion | Result |
|---|---|---|---|
| 07/09/2026 | PUCT | To approve NOGRR282 and accompanying ERCOT Market Impact Statement as presented in Project No. 54445, Review of Protocols Adopted by the Independent Organization | Passed |
| 06/02/2026 | BOARD | To recommend approval of NOGRR282 as recommended by TAC in the 4/29/26 TAC Report as amended by the 5/11/26 ERCOT comments | Passed |
| 04/29/2026 | TAC | To recommend approval of NOGRR282 as recommended by ROS in the 4/2/26 ROS Report as amended by the 4/13/26 ERCOT comments; and the 4/14/26 Revised Impact Analysis | Passed |
| 04/02/2026 | ROS | To recommend approval of NOGRR282 as amended by the 3/27/26 ERCOT comments as revised by ROS and to forward to TAC NOGRR282 and the 11/14/25 Impact Analysis | Passed |
| 12/04/2025 | ROS | To table NOGRR282 and refer the issue to the Dynamics Working Group (DWG) and System Protection Working Group (SPWG) | Passed |
Background
| Status: | Approved |
|---|---|
| Date Posted: | Nov 14, 2025 |
| Sponsor: | ERCOT |
| Urgent: | Yes |
| Sections: | 2.6.4 (new) and 2.14 (new) |
| Description: | This Nodal Operating Guide Revision Request (NOGRR) establishes frequency and voltage ride-through requirements for Large Computational Loads (LCLs). |
| Reason: | Strategic Plan Objective 1 |
Key Documents
Nov 14, 2025 - docx - 43.8 KB
Nov 14, 2025 - docx - 32.9 KB
Dec 5, 2025 - xls - 134.5 KB
Dec 5, 2025 - docx - 44.5 KB
Dec 5, 2025 - docx - 53.8 KB
Dec 18, 2025 - docx - 42 KB
Jan 23, 2026 - docx - 29.4 KB
Jan 30, 2026 - docx - 53.6 KB
Feb 9, 2026 - docx - 63.5 KB
Feb 16, 2026 - docx - 2.4 MB
Feb 18, 2026 - docx - 28.7 KB
Mar 11, 2026 - docx - 109.2 KB
Mar 12, 2026 - docx - 64.9 KB
Mar 18, 2026 - docx - 38.8 KB
Mar 18, 2026 - docx - 26.2 KB
Mar 25, 2026 - docx - 62.2 KB
Mar 27, 2026 - docx - 125.6 KB
Mar 31, 2026 - docx - 2.4 MB
Apr 1, 2026 - docx - 2.4 MB
Apr 1, 2026 - docx - 26 KB
Apr 7, 2026 - xls - 108 KB
Apr 7, 2026 - docx - 56 KB
Apr 13, 2026 - docx - 62.6 KB
Apr 14, 2026 - docx - 63.9 KB
Apr 14, 2026 - docx - 33.2 KB
Apr 24, 2026 - docx - 67.7 KB
Apr 24, 2026 - docx - 201.2 KB
May 4, 2026 - xls - 141 KB
May 4, 2026 - docx - 64.1 KB
May 11, 2026 - docx - 61.4 KB
May 19, 2026 - docx - 61.9 KB
May 21, 2026 - docx - 63.8 KB
Jun 3, 2026 - docx - 64.8 KB
Jun 11, 2026 - docx - 21.1 KB
Jun 12, 2026 - docx - 20.9 KB
Jun 12, 2026 - docx - 20.9 KB
Jun 12, 2026 - docx - 20.9 KB
Jun 12, 2026 - docx - 20.9 KB
Jun 12, 2026 - docx - 21 KB
Jun 12, 2026 - docx - 20.9 KB
Jun 12, 2026 - docx - 20.9 KB
Jun 12, 2026 - docx - 21 KB
Jun 12, 2026 - docx - 21 KB
Jul 8, 2026 - docx - 21 KB
Jul 11, 2026 - docx - 65.8 KB