PGRR122

Summary

Title Reliability Performance Criteria for Loss of Load
Next Group BOARD
Next Step Board for consideration
Status Pending

Action

Date Gov Body Action Taken Next Steps
11/18/2026 TAC Recommended for Approval Board for consideration
11/05/2026 ROS Recommended for Approval TAC for consideration
10/01/2026 ROS Deferred/Tabled ROS for consideration
12/05/2024 ROS Deferred/Tabled ROS for consideration

Voting Record

Date Gov Body Motion Result
11/18/2026 TAC To recommend approval of PGRR122 as recommended by ROS in the 11/5/26 ROS Report and the 11/17/26 Revised Impact Analysis Passed
11/05/2026 ROS To recommend approval of PGRR122 as amended by the 10/30/26 ERCOT comments and to forward to TAC PGRR122 and the 11/11/24 Impact Analysis Passed
10/01/2026 ROS To grant PGRR122 Urgent status and to table PGRR122 Passed
12/05/2024 ROS To table PGRR122 and refer the issue to the Dynamics Working Group (DWG) and the Planning Working Group (PLWG) Passed

Background

Status: Pending
Date Posted: Nov 11, 2024
Sponsor: ERCOT
Urgent: Yes
Sections: 4.1.1.2 and 4.1.1.9 (new)
Description: This Planning Guide Revision Request establishes a new reliability performance criteria that no more than 1,000 MW of Load may be lost for any single contingency, and also specifies how loss of Load is calculated for this criteria.
Reason: Strategic Plan Objective 1