NPRR146
Summary
| Title | ICCP Telemetry Information Submittals |
|---|---|
| Next Group | |
| Next Step | |
| Status | Approved on 06/15/2010 |
| Effective Dates |
12/01/2010
or per the Nodal Protocol Transition Plan http://www.ercot.com/mktrules/protocols (07/01/10 Nodal Protocols Library) 06/30/2011
Section 3.10.1(3) and (6) |
Action
| Date | Gov Body | Action Taken | Next Steps |
|---|---|---|---|
| 02/19/2009 | PRS | Recommended for Approval | TAC consideration of NPRR146 |
| 03/05/2009 | TAC | Deferred/Tabled | TAC consideration of NPRR146 |
| 08/21/2008 | PRS | Referred | PRS language consideration |
| 06/03/2010 | TAC | Recommended for Approval | ERCOT Board consideration of NPRR146 |
| 09/24/2008 | PRS | Recommended for Approval | PRS Impact Analysis review |
| 12/18/2008 | PRS | Recommended for Approval | PRS Impact Analysis review |
| 05/06/2010 | TAC | Deferred/Tabled | TAC consideration of NPRR146 |
| 01/22/2009 | PRS | Deferred/Tabled | PRS Impact Analysis review |
| 11/20/2008 | PRS | Referred | TPTF consideration of NPRR146 |
| 06/15/2010 | BOARD | Approved | |
| 04/08/2010 | TAC | Deferred/Tabled | TAC consideration of NPRR146 |
| 01/06/2010 | TAC | Deferred/Tabled | TAC consideration of NPRR146 |
| 02/04/2010 | TAC | Deferred/Tabled | TAC consideration of NPRR146 |
| 10/23/2008 | PRS | Deferred/Tabled | PRS Impact Analysis review |
Voting Record
| Date | Gov Body | Motion | Result |
|---|---|---|---|
| 02/19/2009 | PRS | To forward the PRS Recommendation Report to TAC and note to TAC that NPRR146 has been approved post-Nodal Go-Live as stated in the 2/18/09 ERCOT comments and therefore would be slated to be in a future release. | Passed |
| 03/05/2009 | TAC | To table NPRR146 pending a recommendation from PRS on the "parking deck" procedure for post-Nodal Go-Live NPRRs and to reevaluate the projected system impacts of NPRR146. | Passed |
| 08/21/2008 | PRS | To refer NPRR146 to the Transition Plan Task Force (TPTF). | Passed |
| 06/03/2010 | TAC | To recommend approval of NPRR146 as amended by the 5/28/10 ERCOT comments and as revised by TAC and to assign a priority of High to the proposed grey boxed language. | Passed |
| 09/24/2008 | PRS | To recommend approval of NPRR146 as amended by TPTF comments dated 9/2/08. | Passed |
| 12/18/2008 | PRS | To recommend approval of NPRR146 as amended by the 12/17/08 TPTF comments. | Passed |
| 05/06/2010 | TAC | To table NPRR146. | Passed |
| 01/22/2009 | PRS | To table NPRR146. | Passed |
| 11/20/2008 | PRS | To refer NPRR146 to TPTF. | Passed |
| 06/15/2010 | BOARD | To approve NPRR146 as recommended by TAC in the 6/3/10 TAC Report. | Passed |
| 04/08/2010 | TAC | To table NPRR146 for one month. | Passed |
| 01/06/2010 | TAC | To table NPRR146 for one month. | Passed |
| 02/04/2010 | TAC | To table NPRR146 indefinitely. | Passed |
| 10/23/2008 | PRS | To table NPRR146 pending the development of an Impact Analysis. | Passed |
Background
| Status: | Approved |
|---|---|
| Date Posted: | Jul 30, 2008 |
| Sponsor: | American Electric Power |
| Urgent: | No |
| Sections: | 3.10.1 |
| Description: | This Nodal Protocol Revision Request (NPRR) requires that changes to an existing Network Operations Model Change Request (NOMCR) that modify only Inter-Control Center Communications Protocol (ICCP) data object names be submitted prior to the completion of the testing for the Network Operations Model. |
| Reason: | In many instances, the RTU configuration and point list is not available three months ahead of equipment change implementation. This change will require Transmission Service Providers (TSPs) and Qualified Scheduling Entities (QSEs) to provide only the real-time ICCP data object names 15 days prior to change and will allow ERCOT adequate opportunity to test the Network Operations Model prior to moving to production. |
Key Documents
Jul 31, 2008 - doc - 102 KB
Aug 8, 2008 - doc - 43.5 KB
Aug 25, 2008 - doc - 105.5 KB
Sep 2, 2008 - xls - 112 KB
Sep 2, 2008 - doc - 66 KB
Sep 10, 2008 - xls - 86.5 KB
Sep 10, 2008 - doc - 51.5 KB
Sep 29, 2008 - doc - 112 KB
Oct 22, 2008 - doc - 39 KB
Oct 27, 2008 - doc - 112 KB
Nov 13, 2008 - doc - 48 KB
Nov 24, 2008 - doc - 114 KB
Dec 17, 2008 - doc - 65.5 KB
Feb 6, 2009 - xls - 86.5 KB
Dec 22, 2008 - doc - 127 KB
Jan 22, 2009 - doc - 44 KB
Jan 22, 2009 - doc - 63.5 KB
Jan 23, 2009 - doc - 124.5 KB
Feb 18, 2009 - doc - 43.5 KB
Feb 20, 2009 - doc - 127.5 KB
Mar 6, 2009 - doc - 146 KB
Jan 7, 2010 - doc - 114 KB
Feb 8, 2010 - doc - 131 KB
Apr 6, 2010 - doc - 79.5 KB
Apr 12, 2010 - doc - 132 KB
May 3, 2010 - doc - 133 KB
May 7, 2010 - doc - 133.5 KB
May 18, 2010 - doc - 69 KB
May 28, 2010 - doc - 61 KB
Jun 4, 2010 - doc - 179 KB
Jun 4, 2010 - doc - 69 KB
Jun 4, 2010 - doc - 44 KB
Jun 17, 2010 - doc - 174 KB
May 26, 2011 - doc - 43.5 KB
Jun 3, 2011 - doc - 61.5 KB
Jul 22, 2011 - doc - 61.5 KB