NPRR1106
Summary
| Title | Deployment of Emergency Response Service (ERS) Prior to Declaration of Energy Emergency Alert (EEA) |
|---|---|
| Next Group | |
| Next Step | |
| Status | Approved on 12/16/2021 |
| Effective Dates |
12/17/2021
|
Action
| Date | Gov Body | Action Taken | Next Steps |
|---|---|---|---|
| 12/16/2021 | PUCT | Approved | |
| 12/10/2021 | BOARD | Recommended for Approval | Revision Request Consideration |
| 11/29/2021 | TAC | Recommended for Approval | Revision Request Consideration |
| 11/10/2021 | PRS | Recommended for Approval | Revision Request Consideration |
Voting Record
| Date | Gov Body | Motion | Result |
|---|---|---|---|
| 12/16/2021 | PUCT | to approve NPRR1106 and accompanying ERCOT Market Impact Statement as presented in Project No. 52307, Review of Rules Adopted by the Independent Organization in Calendar Year 2021 | Passed |
| 12/10/2021 | BOARD | to recommend approval of NPRR1106 as recommended by TAC in the 11/29/21 TAC Report | Passed |
| 11/29/2021 | TAC | to recommend approval of NPRR1106 as recommended by PRS in the 11/10/21 PRS Report with a recommended effective date of upon PUCT approval (12/17/21) | Passed |
| 11/10/2021 | PRS | To waive notice for NPRR1106; to grant NPRR1106 Urgent status; to recommend approval of NPRR1106 as submitted, and to forward to TAC NPRR1106 and the Impact Analysis | Passed |
Background
| Status: | Approved |
|---|---|
| Date Posted: | Nov 4, 2021 |
| Sponsor: | ERCOT |
| Urgent: | Yes |
| Sections: | 2.1, 3.14.3, 6.5.9.4.1, 6.5.9.4.2, 6.5.9.4.3, 8.1.3.1.3.1, and 8.1.3.1.3.2 |
| Description: | This Nodal Protocol Revision Request (NPRR) revises the Protocols to allow for the deployment of ERS prior to the declaration of an EEA when Physical Responsive Capability (PRC) falls below 3,000 MW and is not projected to be recovered above 3,000 MW within 30 minutes following the deployment of Non-Spin. |
| Reason: | Addresses current operational issues; Market efficiencies or enhancements; Regulatory requirements |
Key Documents
Nov 4, 2021 - docx - 60.3 KB
Nov 4, 2021 - docx - 18.1 KB
Nov 15, 2021 - xls - 143.5 KB
Nov 15, 2021 - xls - 101 KB
Nov 15, 2021 - docx - 62 KB
Dec 1, 2021 - xls - 144 KB
Dec 1, 2021 - docx - 62.7 KB
Dec 10, 2021 - docx - 62.3 KB
Dec 16, 2021 - docx - 62.7 KB