NOGRR204
Summary
| Title | Related to NPRR989, BESTF-1 Energy Storage Resource Technical Requirements |
|---|---|
| Next Group | |
| Next Step | |
| Status | Approved on 06/09/2020 |
Action
| Date | Gov Body | Action Taken | Next Steps |
|---|---|---|---|
| 06/09/2020 | BOARD | Approved | |
| 05/29/2020 | TAC | Recommended for Approval | Board for consideration |
| 05/11/2020 | ROS | Recommended for Approval | TAC for consideration |
| 03/09/2020 | ROS | Recommended for Approval | ROS for Impact Analysis consideration |
| 01/09/2020 | ROS | Deferred/Tabled | ROS for consideration |
Voting Record
| Date | Gov Body | Motion | Result |
|---|---|---|---|
| 06/09/2020 | BOARD | To approve NOGRR204 as recommended by TAC in the 5/29/20 TAC Report | Passed |
| 05/29/2020 | TAC | To grant NOGRR204 Urgent status and recommend approval of NOGRR204 as recommended by ROS in the 5/11/20 ROS Report | Passed |
| 05/11/2020 | ROS | To endorse and forward to TAC the 3/9/20 ROS Report and Impact Analysis for NOGRR204 | Passed |
| 03/09/2020 | ROS | To recommend approval of NOGRR204 as amended by the 2/28/20 ERCOT comments | Passed |
| 01/09/2020 | ROS | To table NOGRR204 and refer the issue to the Operations Working Group (OWG) and the Performance, Disturbance, Compliance Working Group (PDCWG) | Passed |
Background
| Status: | Approved |
|---|---|
| Date Posted: | Dec 16, 2019 |
| Sponsor: | ERCOT |
| Urgent: | Yes |
| Sections: | 2.2.5, 2.2.7, 2.2.8, 2.2.10, 2.3, 2.6.2, 2.7, 2.7.1, 2.7.2, 2.7.3.2, 2.7.3.3, 2.7.3.4, 2.7.3.5, 2.9, 2.9.1, 3.3.2.1, 3.3.2.2, 6.2.6.3.4, 8C, and 8J |
| Description: | This Nodal Operating Guide Revision Request (NOGRR) establishes technical requirements for Energy Storage Resources (ESRs) in the following areas: Reactive Power capability, including performance requirements during transient voltage disturbances, and testing criteria; voltage ride-through requirements; frequency ride-through requirements; and Governor Dead-Band and droop setting requirements. |
| Reason: | Addresses current operational issues. Market efficiencies or enhancements. |
Key Documents
Dec 16, 2019 - docx - 415.4 KB
Dec 16, 2019 - docx - 28.9 KB
Jan 13, 2020 - docx - 417 KB
Feb 28, 2020 - docx - 399.8 KB
Mar 11, 2020 - xls - 122.5 KB
Mar 11, 2020 - docx - 418.6 KB
May 14, 2020 - xls - 122.5 KB
May 14, 2020 - docx - 420.5 KB
Jun 1, 2020 - xls - 130.5 KB
Jun 1, 2020 - docx - 421.3 KB
Jun 11, 2020 - docx - 421.4 KB