MIS LOG IN

Operations Messages

This section contains important messages from the ERCOT Control Room. Refresh this screen to see current operation messages. 

Nov 2023 Dec 2023 Jan 2024 Feb 2024 Mar 2024 Apr 2024
Date & Time Notice Type Status
Feb 29, 2024 8:47:27 AM The Daily RSASM for Thursday, February 29, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 29, 2024 12:03:34 AM On 02/28/2024, a sudden loss of generation occurred at 02:29 totaling 534.04 MW. Frequency declined to 59.918 Hz, ERCOT load was 38,846 MW. Another sudden loss of generation occurred at 10:15 totaling 603.50 MW. Frequency declined to 59.901 Hz, ERCOT load was 46,321 MW. Operational Information Active
Feb 28, 2024 10:19:13 AM ERCOT ECRS HAS BEEN RECALLED Operational Information Cancelled
Feb 28, 2024 10:16:05 AM ERCOT ECRS HAS BEEN DEPLOYED Operational Information Active
Feb 28, 2024 8:48:05 AM The Daily RSASM for Wednesday, February 28, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 28, 2024 12:08:17 AM On 02/27/2024, a sudden loss of generation occurred at 09:21:15 totaling 760.59 MW. Frequency declined to 59.845 Hz, ERCOT load was 45,867 MW. Operational Information Active
Feb 27, 2024 9:28:29 AM ERCOT ECRS HAS BEEN RECALLED Operational Information Cancelled
Feb 27, 2024 9:21:17 AM ERCOT ECRS HAS BEEN DEPLOYED Operational Information Active
Feb 27, 2024 8:47:59 AM The Daily RSASM for Tuesday, February 27, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 27, 2024 1:41:53 AM ERCOT has cancelled the following notice: ERCOT will execute a SASM at 01:15 for operating day 2/27/2024 for Reg Down for HE 5 in the amount of 5.4MW, HE 7 in the amount of 14.8 MW, HE 8 in the amount of 53.7 MW, and HE 9 in the amount of 32.7 MW. Operational Information Cancelled
Feb 27, 2024 12:30:55 AM ERCOT will execute a SASM at 01:15 for operating day 2/27/2024 for Reg Down for HE 5 in the amount of 5.4MW, HE 7 in the amount of 14.8 MW, HE 8 in the amount of 53.7 MW, and HE 9 in the amount of 32.7 MW. Operational Information Active
Feb 27, 2024 12:00:54 AM No sudden loss of generation greater than 450 MW occurred on February 26, 2024. Operational Information Active
Feb 26, 2024 8:48:27 AM The Daily RSASM for Monday, February 26, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 26, 2024 12:06:31 AM No sudden loss of generation greater than 450 MW occurred on February 25, 2024. Operational Information Active
Feb 25, 2024 8:48:06 AM The Daily RSASM for Sunday, February 25, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 25, 2024 12:26:30 AM ERCOT has cancelled the following notice: ERCOT will execute a SASM at 00:05 for operating day 02/25/24 for HE06 for 2.1 MW REGDN and 9.7 MW REGUP, for HE08 for 43.6 MW REGDN, and for HE09 for 54.5 MW REGDN Operational Information Cancelled
Feb 25, 2024 12:02:02 AM No sudden loss of generation greater than 450 MW occurred on February 24, 2024. Operational Information Active
Feb 24, 2024 11:30:32 PM ERCOT will execute a SASM at 00:05 for operating day 02/25/24 for HE06 for 2.1 MW REGDN and 9.7 MW REGUP, for HE08 for 43.6 MW REGDN, and for HE09 for 54.5 MW REGDN Operational Information Active
Feb 24, 2024 8:48:29 AM The Daily RSASM for Saturday, February 24, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 24, 2024 12:02:03 AM No sudden loss of generation greater than 450 MW occurred on February 23, 2024. Operational Information Active
Feb 23, 2024 2:44:21 PM The DC_L (Laredo VFT) DC Tie will be unavailable from 03/04/2024 08:00 through 03/15/2024 16:00 due to a planned outage. Operational Information Active
Feb 23, 2024 8:48:32 AM The Daily RSASM for Friday, February 23, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 23, 2024 12:48:10 AM No sudden loss of generation greater than 450 MW occurred on February 22, 2024. Operational Information Active
Feb 22, 2024 8:48:58 AM The Daily RSASM for Thursday, February 22, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 22, 2024 8:32:10 AM ERCOT has cancelled the following notice: ERCOT taking manual action to mitigate transmission congestion in Rio Grande Valley area. Operational Information Cancelled
Feb 22, 2024 12:05:45 AM No sudden loss of generation greater than 450 MW occurred on February 21, 2024. Operational Information Active
Feb 21, 2024 8:47:41 AM The Daily RSASM for Wednesday, February 21, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 21, 2024 6:10:18 AM ERCOT taking manual action to mitigate transmission congestion in Rio Grande Valley area. Operational Information Active
Feb 21, 2024 12:20:38 AM No sudden loss of generation greater than 450 MW occurred on February 20, 2024. Operational Information Active
Feb 20, 2024 6:16:35 PM ERCOT has cancelled the following notice: ERCOT taking manual action to mitigate transmission congestion in Rio Grande Valley area. Operational Information Cancelled
Feb 20, 2024 6:09:32 PM ERCOT taking manual action to mitigate transmission congestion in Rio Grande Valley area. Operational Information Active
Feb 20, 2024 4:21:40 PM ERCOT has cancelled the following notice: ERCOT taking manual action to mitigate transmission congestion in Rio Grande Valley area. Operational Information Cancelled
Feb 20, 2024 3:51:21 PM ERCOT taking manual action to mitigate transmission congestion in Rio Grande Valley area. Operational Information Active
Feb 20, 2024 8:47:16 AM The Daily RSASM for Tuesday, February 20, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 20, 2024 12:19:22 AM No sudden loss of generation greater than 450 MW occurred on February 19, 2024. Operational Information Active
Feb 19, 2024 6:50:56 PM ERCOT has cancelled the following notice: At 18:33 approximately 550 MW total of Non-Spin has been Recalled, and Approximately 845 MWs remain deployed with anticipated duration is 23:59:00 . Operational Information Cancelled
Feb 19, 2024 6:50:44 PM At 18:50, All Non-Spin has been recalled. Operational Information Active
Feb 19, 2024 6:50:26 PM ERCOT has cancelled the following notice: At 17:55 approximately 1392 MW total of Non-Spin has been deployed, anticipated duration is 23:59:00. Operational Information Cancelled
Feb 19, 2024 6:50:02 PM CM-ASM-NOTF AS_TYPE: Non-Spin, DEPLOY_MW: 0.0, BEGIN_TIME: 2024-02-19 18:50:02, END_TIME: 2024-02-19 18:50:02, DURATION: 0 Hrs 0 Mins.; Operational Information
Feb 19, 2024 6:39:07 PM At 18:33 approximately 550 MW total of Non-Spin has been Recalled, and Approximately 845 MWs remain deployed with anticipated duration is 23:59:00 . Operational Information Active
Feb 19, 2024 6:33:46 PM CM-ASM-NOTF AS_TYPE: Non-Spin, DEPLOY_MW: 844.7, BEGIN_TIME: 2024-02-19 19:00:00, END_TIME: 2024-02-19 23:59:00, DURATION: 4 Hrs 59 Mins.; Operational Information
Feb 19, 2024 6:33:02 PM CM-ASM-NOTF AS_TYPE: Non-Spin, DEPLOY_MW: 1399.6, BEGIN_TIME: 2024-02-19 19:00:00, END_TIME: 2024-02-19 23:59:00, DURATION: 4 Hrs 59 Mins.; Operational Information
Feb 19, 2024 5:57:56 PM At 17:55 approximately 1392 MW total of Non-Spin has been deployed, anticipated duration is 23:59:00. Operational Information Active
Feb 19, 2024 5:55:32 PM CM-ASM-NOTF AS_TYPE: Non-Spin, DEPLOY_MW: 1392.4, BEGIN_TIME: 2024-02-19 17:55:32, END_TIME: 2024-02-19 23:59:00, DURATION: 6 Hrs 3 Mins.; Operational Information
Feb 19, 2024 5:47:07 PM At 17:46 approximately 839 MW of Non-Spin has been deployed, anticipated duration is 23:59:00. Operational Information Active
Feb 19, 2024 5:46:07 PM CM-ASM-NOTF AS_TYPE: Non-Spin, DEPLOY_MW: 839.0, BEGIN_TIME: 2024-02-19 17:46:06, END_TIME: 2024-02-19 23:59:00, DURATION: 6 Hrs 12 Mins.; Operational Information
Feb 19, 2024 5:44:55 PM ERCOT has cancelled the following notice: ERCOT taking manual action to mitigate transmission congestion in Rio Grand Valley area. Operational Information Cancelled
Feb 19, 2024 5:37:57 PM ERCOT taking manual action to mitigate transmission congestion in Rio Grand Valley area. Operational Information Active
Feb 19, 2024 8:47:18 AM The Daily RSASM for Monday February 19, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 19, 2024 12:16:19 AM No sudden loss of generation greater than 450 MW occurred on February 18, 2024. Operational Information Active
Feb 19, 2024 12:00:50 AM ERCOT has cancelled the following notice: The DC_E (East) DC Tie will be unavailable from 02/18/2024 23:00 through 02/19/2024 09:00 due to a forced outage. Operational Information Cancelled
Feb 18, 2024 11:11:23 PM The DC_E (East) DC Tie will be unavailable from 02/18/2024 23:00 through 02/19/2024 09:00 due to a forced outage. Operational Information Active
Feb 18, 2024 11:11:40 AM ERCOT has cancelled the following notice: ERCOT is taking manual actions to pre-posture to prevent for a 345 KV Forced outage in the West Texas area. Operational Information Cancelled
Feb 18, 2024 9:08:25 AM ERCOT is taking manual actions to pre-posture to prevent for a 345 KV Forced outage in the West Texas area. Operational Information Active
Feb 18, 2024 9:08:09 AM ERCOT has cancelled the following notice: ERCOT is taking manual actions to pre-posture for a 345 KV Forced outage in the West Texas area. Operational Information Cancelled
Feb 18, 2024 8:53:58 AM ERCOT is taking manual actions to pre-posture for a 345 KV Forced outage in the West Texas area. Operational Information Active
Feb 18, 2024 8:51:53 AM The Daily RSASM for Sunday, February 18, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 18, 2024 12:02:13 AM No sudden loss of generation greater than 450 MW occurred on February 17, 2024. Operational Information Active
Feb 17, 2024 8:48:03 AM The Daily RSASM for Saturday, February 17, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 17, 2024 12:01:25 AM No sudden loss of generation greater than 450 MW occurred on February 16, 2024. Operational Information Active
Feb 16, 2024 2:12:38 PM DAM is complete, DRUC will begin at 1510. Operational Information Active
Feb 16, 2024 1:19:21 PM ERCOT has postponed the deadline for the posting of the DAM solution for Operating Day 02/17/2024 due to long solution run time. Advisory Active
Feb 16, 2024 8:55:21 AM The Daily RSASM for Friday, February 16, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 16, 2024 12:30:36 AM No sudden loss of generation greater than 450 MW occurred on February 15, 2024. Operational Information Active
Feb 15, 2024 8:56:13 AM The Daily RSASM for Thursday, February 15, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 15, 2024 12:07:27 AM No sudden loss of generation greater than 450 MW occurred on February 14, 2024. Operational Information Active
Feb 14, 2024 8:49:02 AM The Daily RSASM for Wednesday, February 14, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 14, 2024 7:17:23 AM ERCOT has cancelled the following notice: ERCOT will execute a SASM at 06:40 for operating day 02/14/2024 for 18.5 MW RRS HE 12-16. Operational Information Cancelled
Feb 14, 2024 6:04:30 AM ERCOT will execute a SASM at 06:40 for operating day 02/14/2024 for 18.5 MW RRS HE 12-16. Operational Information Active
Feb 14, 2024 2:17:01 AM ERCOT has cancelled the following notice: ERCOT will execute a SASM at 02:00 for operating day 02/14/24 for HE05-06 for 18.5 MW RRS Operational Information Cancelled
Feb 14, 2024 1:35:18 AM No sudden loss of generation greater than 450 MW occurred on February 13, 2024. Operational Information Active
Feb 14, 2024 1:27:58 AM ERCOT will execute a SASM at 02:00 for operating day 02/14/24 for HE05-06 for 18.5 MW RRS Operational Information Active
Feb 13, 2024 6:39:51 PM ERCOT has cancelled the following notice: ERCOT will execute a SASM at 18:25 for operating day 02/13/24 for HE23-24 for 14.5 MW ECRS Operational Information Cancelled
Feb 13, 2024 5:55:03 PM ERCOT has cancelled the following notice: ERCOT is taking manual actions for a Basecase in the South Central area. Operational Information Cancelled
Feb 13, 2024 5:50:00 PM ERCOT will execute a SASM at 18:25 for operating day 02/13/24 for HE23-24 for 14.5 MW ECRS Operational Information Active
Feb 13, 2024 9:02:07 AM ERCOT is taking manual actions for a Basecase in the South Central area. Operational Information Active
Feb 13, 2024 8:50:03 AM The Daily RSASM for Tuesday, February 13, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 13, 2024 3:34:49 AM ERCOT has cancelled the following notice: ERCOT will execute a SASM at 03:10 for operating day 02/13/24 for ECRS: 14.5 MW for HE06-22 and for NSPIN in the following amounts: 40.6 MW for HE06, 24.6 MW for HE08, 30.6 MW for HE09-15, 36.1 MW for HE16, 40.6 MW for HE17-18, 30.6 MW for HE19-22 Operational Information Cancelled
Feb 13, 2024 2:37:33 AM ERCOT will execute a SASM at 03:10 for operating day 02/13/24 for ECRS: 14.5 MW for HE06-22 and for NSPIN in the following amounts: 40.6 MW for HE06, 24.6 MW for HE08, 30.6 MW for HE09-15, 36.1 MW for HE16, 40.6 MW for HE17-18, 30.6 MW for HE19-22 Operational Information Active
Feb 13, 2024 12:07:06 AM No sudden loss of generation greater than 450 MW occurred on February 12, 2024. Operational Information Active
Feb 12, 2024 5:45:23 PM ERCOT has cancelled the following notice: ERCOT is taking manual actions for a Basecase in the South Central area. Operational Information Cancelled
Feb 12, 2024 10:01:11 AM ERCOT is taking manual actions for a Basecase in the South Central area. Operational Information Active
Feb 12, 2024 8:49:20 AM The Daily RSASM for Monday, February 12, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 12, 2024 12:03:28 AM No sudden loss of generation greater than 450 MW occurred on February 11, 2024. Operational Information Active
Feb 11, 2024 8:47:20 AM The Daily RSASM for Sunday, February 11, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 11, 2024 6:09:34 AM ERCOT has cancelled the following notice: ERCOT will execute a SASM at [0535] for operating day [02/11/2024] for HE [8 through 11] for [18.5] MW [RRS]. Operational Information Cancelled
Feb 11, 2024 5:09:57 AM ERCOT will execute a SASM at [0535] for operating day [02/11/2024] for HE [8 through 11] for [18.5] MW [RRS]. Operational Information Active
Feb 11, 2024 12:12:04 AM No sudden loss of generation greater than 450 MW occurred on February 10, 2024. Operational Information Active
Feb 10, 2024 8:46:00 AM The Daily RSASM for Saturday, February 10, 2024 will not be occurring due to zero participating QSEs. Advisory Active
Feb 10, 2024 12:11:46 AM No sudden loss of generation greater than 450 MW occurred on February 9, 2024. Operational Information Active
Feb 9, 2024 8:46:50 AM The Daily RSASM for Friday, February 9, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 9, 2024 12:00:04 AM No sudden loss of generation greater than 450 MW occurred on February 8, 2024. Operational Information Active
Feb 8, 2024 8:47:12 AM The Daily RSASM for Thursday, February 8, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 8, 2024 12:06:58 AM No sudden loss of generation greater than 450 MW occurred on February 7, 2024. Operational Information Active
Feb 7, 2024 9:00:23 AM The Daily RSASM for Wednesday, February 7, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 7, 2024 12:20:25 AM No sudden loss of generation greater than 450 MW occurred on February 6, 2024. Operational Information Active
Feb 6, 2024 2:07:08 PM ERCOT has cancelled the following notice: ERCOT is taking manual actions for a 345 KV outage in the South Texas area. Operational Information Cancelled
Feb 6, 2024 10:21:30 AM ERCOT is taking manual actions for a 345 KV outage in the South Texas area. Operational Information Active
Feb 6, 2024 8:50:01 AM The Daily RSASM for Tuesday, February 6, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 6, 2024 3:57:32 AM ERCOT is working from primary control center. Operational Information Active
Feb 6, 2024 3:56:19 AM ERCOT has cancelled the following notice: ERCOT will be working from the alternate control center until further notice, use the OPX numbers for Bastrop. Operational Information Cancelled
Feb 6, 2024 12:00:04 AM No sudden loss of generation greater than 450 MW occurred on February 5, 2024. Operational Information Active
Feb 5, 2024 4:01:34 PM ERCOT will be working from the alternate control center until further notice, use the OPX numbers for Bastrop. Operational Information Active
Feb 5, 2024 9:00:43 AM The Daily RSASM for Monday, February 5, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 5, 2024 12:04:06 AM No sudden loss of generation greater than 450 MW occurred on February 4, 2024. Operational Information Active
Feb 4, 2024 9:13:44 PM ERCOT has cancelled the following notice: ERCOT will execute a SASM at [2035] for operating day [02/04/2024 ] HE [23 and 24] for 2 MW’s of NSPIN, and for operating day [02/05/2024] for HE [1-3] for 2 MW of NSPIN for HE [4-6] for 3 MW’s of NSPIN. Operational Information Cancelled
Feb 4, 2024 8:16:09 PM ERCOT will execute a SASM at [2035] for operating day [02/04/2024 ] HE [23 and 24] for 2 MW’s of NSPIN, and for operating day [02/05/2024] for HE [1-3] for 2 MW of NSPIN for HE [4-6] for 3 MW’s of NSPIN. Operational Information Active
Feb 4, 2024 8:15:11 PM ERCOT has cancelled the following notice: ERCOT will execute a SASM at [2035] for operating day [02/04/2024 ] HE [23 and 24] for 2 MW’s of NSPIN, and for operating day [02/05/2024] for HE [1-3] for 2 MW of NSPIN for HE [3-6] for 3 MW’s of NSPIN. Operational Information Cancelled
Feb 4, 2024 8:10:50 PM ERCOT will execute a SASM at [2035] for operating day [02/04/2024 ] HE [23 and 24] for 2 MW’s of NSPIN, and for operating day [02/05/2024] for HE [1-3] for 2 MW of NSPIN for HE [3-6] for 3 MW’s of NSPIN. Operational Information Active
Feb 4, 2024 8:48:36 AM The Daily RSASM for Sunday, February 4, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 4, 2024 12:03:30 AM No sudden loss of generation greater than 450 MW occurred on February 3, 2024. Operational Information Active
Feb 3, 2024 8:48:54 AM The Daily RSASM for Saturday, February 3, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 3, 2024 12:23:35 AM No sudden loss of generation greater than 450 MW occurred on February 2, 2024. Operational Information Active
Feb 2, 2024 10:46:44 AM ERCOT has cancelled the following notice: ERCOT is taking manual actions to pre-posture for a 138 KV outage in the Far West area. Operational Information Cancelled
Feb 2, 2024 8:47:44 AM The Daily RSASM for Friday, February 2, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 2, 2024 8:41:27 AM ERCOT is taking manual actions to pre-posture for a 138 KV outage in the Far West area. Operational Information Active
Feb 2, 2024 12:40:38 AM No sudden loss of generation greater than 450 MW occurred on February 1, 2024. Operational Information Active
Feb 1, 2024 8:47:29 AM The Daily RSASM for Thursday, February 1, 2024 will not be occurring due to zero participating QSEs. Operational Information Active
Feb 1, 2024 12:33:49 AM No sudden loss of generation greater than 450 MW occurred on January 31, 2024. Operational Information Active