PRR824
| Title: |
Primary Frequency Response from WGRs
|
| Next Group: |
|
| Next Step: |
|
| Status: |
Approved
on 12/15/2009
|
| Date |
Gov Body |
Motion |
Result |
Against |
Abstentions |
|
12/15/2009
|
Board of Directors
|
To approve PRR824 as recommended by TAC in the 11/5/09 TAC Recommendation Report
|
Passed
|
|
|
|
11/05/2009
|
TAC
|
To recommended approval of PRR824 as recommended by PRS in the 10/22/09 PRS Recommendation Report and as revised by the 10/28/09 ERCOT comments
|
Passed
|
0
|
0
|
|
10/22/2009
|
PRS
|
To endorse and forward the 9/17/09 PRS Recommendation Report as revised by PRS and Impact Analysis to TAC
|
Passed
|
0
|
0
|
|
09/17/2009
|
PRS
|
To recommend approval of PRR824 as amended by the 9/16/09 CPS Energy comments and as revised by PRS
|
Passed
|
1 Indep Gen
|
|
|
08/25/2009
|
PRS
|
To table PRR824 for one month
|
Passed
|
0
|
0
|
Vote tallies here reflect individual votes, not the weight of the votes by market segment. Affirmative votes are not recorded in these vote tallies. For additional details on the voting record, please consult the Recommendation or Action Report, or the official vote tally if available, as posted in the key documents.
| Status: |
Approved
|
| Date Posted: |
07/21/2009
|
| Sponsor: |
Rick Keetch on behalf of the Reliability and Operations Subcommittee (ROS)
|
| Urgent: |
No
|
| Sections: |
2.1, 5.9.1.1, 5.9.1.3 (new)
|
| Description: |
This Protocol Revision Request (PRR) adds a requirement for wind generator control systems to be programmed to respond to frequency deviations by controlling WGR real power output in a way that is similar to governor response for conventional generators.
|
| Reason: |
As WGRs displace more and more conventional generation, there will be a growing need for WGRs to replace the primary frequency response capability not being provided by the Off-line conventional generators. WGR primary frequency response shall be of particular value if frequency increases occur.
|
-
(07/21/09, .doc, 83.5 KB)
-
(08/12/09, .doc, 71.5 KB)
-
(08/13/09, .doc, 72 KB)
-
(08/24/09, .doc, 152.5 KB)
-
(08/25/09, .doc, 39 KB)
-
(08/27/09, .doc, 80.5 KB)
-
(08/31/09, .doc, 42 KB)
-
(09/10/09, .doc, 82.5 KB)
-
(09/11/09, .doc, 47.5 KB)
-
(09/16/09, .doc, 41.5 KB)
-
(09/16/09, .doc, 89 KB)
-
(09/22/09, .doc, 122 KB)
-
(10/19/09, .doc, 43 KB)
-
(10/26/09, .doc, 122.5 KB)
-
(10/28/09, .doc, 85 KB)
-
(11/06/09, .doc, 126 KB)
-
(12/16/09, .doc, 128 KB)