PRR647
| Date | Gov Body | Action Taken | Next Steps | |
|---|---|---|---|---|
| 01/16/2007 | Board of Directors |
|
Approved | |
| 12/01/2006 | TAC |
|
Recommended for Approval | Board consideration |
| 11/16/2006 | PRS |
|
Recommended for Approval | TAC consideration |
| 09/21/2006 | PRS |
|
Recommended for Approval | Review of Impact Analysis |
| 03/23/2006 | PRS |
|
Referred | Analysis |
| 01/19/2006 | PRS |
|
Referred | ROS review and report back to PRS in March |
| 12/16/2005 | PRS | January PRS initial review | ||
| Date | Gov Body | Motion | Result | Against | Abstentions |
|---|---|---|---|---|---|
| 01/16/2007 | Board of Directors | Approved as recommended by TAC. | Passed | 0 | 0 |
| 12/01/2006 | TAC | Recommend approval of PRR647 as recommended by PRS and to have this PRR implemented as soon as practicable within 18 months, but no later than 1/1/09, if such delay is necessary to accommodate nuclear plants. | Passed | 0 | 0 |
| 11/16/2006 | PRS | Motion to forward the IA, CBA and Recommendation Report to TAC for consideration. | Passed | 0 | 1 Independent Generator |
| 09/21/2006 | PRS | Recommend approval as revised by OWG comments. | Passed | 0 | 1 MOU |
| 03/23/2006 | PRS | Instruct ROS to develop a cost benefit assessment to include an assessment of the effect on system reliability, and to investigate potential alternatives to implementing this PRR | Passed | 0 | 0 |
| 01/19/2006 | PRS | Refer PRR647 to ROS for determination of ERCOT needs and identification of data already being reported to ERCOT by Market Participants, and direct ROS to report to PRS at its March meeting | Passed |
Vote tallies here reflect individual votes, not the weight of the votes by market segment. Affirmative votes are not recorded in these vote tallies. For additional details on the voting record, please consult the Recommendation or Action Report, or the official vote tally if available, as posted in the key documents.
| Status: | Approved |
| Date Posted: | 12/05/2005 |
| Sponsor: | ERCOT |
| Urgent: | No |
| Sections: | 6.5.1.1 |
| Description: | Adds a requirement for a QSE representing a Resource to supply both gross and net MW and Mvar data to ERCOT for use in the operations model. |
| Reason: |
(1) In order to correctly model reactive capability and assess voltage security with ERCOTâ??s Voltage Stability Analysis Tool (VSAT), it is necessary to know the gross (generator terminal) output of Generation Resources, both MW and Mvar. (2) This PRR provides for compliance with NERC Standard VAR-001-0: R9, which states â?? Each Generator Operator shall provide information to its Transmission Operator on the status of all generation reactive power resources, including the status of voltage regulators and power system stabilizers. |
-
(12/05/05, .doc, 102.5 KB)
-
(12/05/05, .doc, 41 KB)
-
(12/13/05, .doc, 73 KB)
-
(12/14/05, .doc, 100 KB)
-
(12/15/05, .doc, 83.5 KB)
-
(01/05/06, .doc, 109 KB)
-
(01/11/06, .doc, 76.5 KB)
-
(01/17/06, .doc, 80 KB)
-
(01/20/06, .doc, 106 KB)
-
(01/18/06, .ppt, 116.5 KB)
-
(03/28/06, .doc, 105.5 KB)
-
(05/12/06, .doc, 79.5 KB)
-
(07/11/06, .doc, 74.5 KB)
-
(07/21/06, .doc, 72.5 KB)
-
(11/17/06, .doc, 103 KB)
-
(10/12/06, .doc, 43.5 KB)
-
(10/11/06, .xls, 137.5 KB)
-
(11/09/06, .xls, 138 KB)
-
(01/19/07, .doc, 107 KB)
-
(01/23/07, .doc, 109.5 KB)