MIS LOG IN

PRR733

Summary

Title Remove 168-Hour Generation Testing Requirement
Next Group
Next Step
Status Approved on 11/13/2007
Effective Dates
12/01/2007

Action

Date Gov Body Action Taken Next steps
11/13/2007 BOARD Approved
10/05/2007 TAC Recommended for Approval Board consideration of PRR733
09/20/2007 PRS Recommended for Approval Consideration of PRR733 by TAC.
08/23/2007 PRS Recommended for Approval Review of the Impact Analysis

Voting Record

Date Gov Body Motion Result
11/13/2007 BOARD To approve as recommended by TAC. Passed
10/05/2007 TAC Recommend approval of PRR733 as submitted by PRS. Passed
09/20/2007 PRS To forward the Impact Analysis and Recommendation Report for PRR733 to TAC. Passed
08/23/2007 PRS Recommend approval of PRR733 as revised by PRS. Passed

Background

Status: Approved
Date Posted: Jul 9, 2007
Sponsor: ERCOT Staff
Urgent: No
Sections: 6.10.2, General Capacity Testing Requirements
Description: This PRR will remove the 168 hour requirement and the need to utilize the observed actual output in the first 168 hours, if test data is not provided.
Reason: The current language could result in undesirable restrictions on unit capability and is not currently done due to lack of tracking software. The proposed PRR will provide language that more closely agrees with actual practice and clarifies the need for relevant Resource data.

Key Documents