Back to Daily Grid
Operations Reports

Daily Grid Operations Report
09/04/2008

Peak Load 51892
Peak Hour 18
Planned Peak 52814
Planned Peak Hour 17

Constraints Encountered During the Day

Start Constraint Reason
00:15 OOME Monticello down Monticello SES - Allen Switch & Sulphur Springs Switch 345kV overloads Farmerville TU - Royse Switch 345kV - 110% of 1072 MVA.
01:15 Calaveras - Ball Park OC3 Loss of Calaveras - Ball Park 138kV overloads Five Points - Westside CPS - 111% of 215 MVA rating.
03:00 OOME Calaveras JT Dealy down Loss of Calaveras - Ball Park 138kV overloads Five Points - Westside CPS - 109% of 215 MVA rating.
08:00 OOMC Silas Ray on Planned transmission outage.
12:00 OOME Decker up Loss of Austrop 345/138KV autotransformer #2 overloads Austrop 345/138KV autotransformer #1 - 101% of 480 MVA rating.
12:30 OOME Gideon up Loss of Austrop 345/138KV autotransformer #2 overloads Austrop 345/138KV autotransformer #1 - 101% of 480 MVA rating.
13:45 OOME Laredo up  Loss of Derby - Pearsall 138KV overloads Derby - Pearsall 69KV - 108% of 40 MVA rating.
14:00 Odessa EHV Transformer OC3 Loss of Odessa EHV 345/138KV autotransformer #1 overloads Odessa 345/138KV autotransformer #2 - 102% of 520 MVA rating.
15:45 Trinidad - Stryker Creek - Mount Enterprise OC3 Loss of Trinidad - Stryker Creek - Mount Enterprise 345KV overloads Southeast Nacogdoches 345/138KV transformer - 107% of 512 MVA rating.
23:15 Marion - Zorn and Clear Springs OC3 Loss of Marion - Zorn and Clear Springs 345kV overloads Seguin - Seguin West 138kV - 109% of 220 MVA rating.

Other Notable Events

Start End Event
00:15 24:00 Alert Level Yellow Elevated